IEC 62271-104-2015 高壓開(kāi)關(guān)設備和控制設備--第104部分:額定電壓大于52千伏的交流開(kāi)關(guān) High-voltage switchgear and controlgear - Part 104: Alternating current switches for rated voltages higher than 52 kV
- 標準類(lèi)別:
- 標準大?。?/li>
- 標準編號:IEC 62271-104-2015
- 標準狀態(tài):現行
- 更新時(shí)間:2023-12-03
- 下載次數:次
Subclause 1.1 of IEC 62271-1:2007 is not applicable, and is replaced as follows:
This part of IEC 62271 is applicable to three-pole alternating current switches for rated voltages higher than 52 kV, having making and breaking current ratings, for indoor and outdoor installations, and for rated frequencies up to and including 60 Hz.
This standard is also applicable to the operating devices of these switches and to their auxiliary equipment.
NOTE 1 Switches for gas insulated switchgear are covered by this standard.
NOTE 2 Switches having a disconnecting function and called switch-disconnectors are also covered by IEC 62271102.
NOTE 3 Earthing switches are not covered by this standard. Earthing switches forming an integral part of a switch are covered by IEC 62271-102.
The main object of this standard is to establish requirements for switches used in transmission and distribution systems. General-purpose switches for this application are designed to comply with the following service applications:
– arrying rated normal current continuously;
– carrying short-circuit currents for a specified time;
– switching of mainly active loads; – switching of no-load transformers;
– switching of the charging current of unloaded cables, overhead lines or busbars;
– switching of closed-loop circuits;
– making short-circuit currents.
A further object of this standard is to establish requirements for limited-purpose and special- purpose switches used in transmission and distribution systems.
Limited-purpose switches comply with one or more of the service applications indicated above.
Special-purpose switches may comply with one or more of the service applications indicated above and, in addition, are suitable for one or more of the following applications:
– switching single capacitor banks;
– switching back-to-back capacitor banks;
– switching shunt reactors including secondary or tertiary reactors switched from the primary side of the transformer;
– applications requiring an increased number of operating cycles;
– switching under earth fault conditions in non-effectively earthed neutral systems.dition 2.0 2015-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
High-voltage switchgear and controlgear –
Part 104: Alternating current switches for rated voltages higher than 52 kV
Appareillage à haute tension –
Partie 104: Interrupteurs à courant alternatif pour tensions assignées
supérieures à 52 kV
IEC 62271-104:2015-02(en-fr)
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright ? 2015 IEC, Gene
-
GB/T 706-2016熱軋型鋼 2023-12-03
-
GB/T 1094.1-2013電力變壓器 第1部分:總則 2023-12-03
-
JB/T 10216-2013電控配電用電纜橋架 2023-12-03
-
GB 9706.1-2020醫用電氣設備 第1部分:基本安全和基本性能的通用要求 2023-12-03
-
GB/T 10801.2-2018絕熱用擠塑聚苯乙烯泡沫塑料(XPS) 2023-12-03
-
GB/T 13663.2-2018給水用聚乙烯(PE)管道系統 第2部分:管材 2023-12-03
-
GB 51251-2017建筑防煙排煙系統技術(shù)標準 2023-12-03
-
YB/T 4001.1-2019鋼格柵板及配套件 第1部分:鋼格柵板 2023-12-03